| INGEDRIVE LV200 | 
        
        
            | General data | 
        
        
            | Inverter type | 
            Two-level voltage source inverter with LV-IGBT power semiconductors | 
        
        
            | Rectifier type | 
            Diode Front End (DFE) 6P / 12P 
            Active Front End (AFE) | 
        
        
            | Main supply voltage range | 
            380 - 480 VAC | 
            500 - 690 VAC | 
        
        
            | Output power range (1) | 
            335 kW - 1010 kW | 
            415 kW - 1380 kW | 
        
        
            | Supply voltage tolerance | 
            Tipically ± 10% | 
        
        
            | Supply frequency | 
            50 / 60 Hz (± 5 %) | 
        
        
            | Input power factor | 
            0.91 - 0.96 for DFE rectifiers 
            1 for AFE rectifiers | 
        
        
            | Output voltage | 
            0 to supply voltage | 
        
        
            | Output frequency | 
            0 to 120 Hz (higher on request) | 
        
        
            | Efficiency  at rated load | 
            Tipically > 0.97 for DFE rectifiers 
            Tipically > 0.96 for AFE rectifiers | 
        
        
            | Motor types | 
            Induction, synchronous or permanent magnet motor | 
        
        
            | Converter cooling | 
            Air cooled 
             | 
        
        
            | Control properties | 
        
        
            | Control types | 
            VC Vector Control / VF Voltage Frequency (2) | 
        
        
            | Static speed acc. (closed loop) (3) | 
            <0.01% in field weakening / <0.01% at constant flow | 
        
        
            | Static torque acc. (closed loop) (3) | 
            <1 % in field weakening / <1 % at constant flow | 
        
        
            | Static torque acc. (open lloop) (3) | 
            <2 % in field weakening / <2 % at constant flow (for synchronous motors) 
            5 % in field weakening / <3 % at constant flow (for induction motors) | 
        
        
            | Torque response time | 
            < 10 ms | 
        
        
            | Shaft torque ripple (3) | 
            ± 1 %  | 
        
        
            | Drive protection functions | 
            Overcurrent, overvoltage and undervoltage monitoring; earth fault; short circuit detection and protection; semiconductor failure monitoring; cooling supervision; phase loss and others | 
        
        
            | Motor protection functions | 
            Overload (4), Overspeed | 
        
        
            | Environmental Conditions | 
        
        
            | Ambient temp. for storage | 
            - 15 ºC to  + 75 ºC (for empty cooling system in water cooled version) | 
        
        
            | Ambient temp. for transport | 
            - 15 ºC to  + 75 ºC (for empty cooling system in water cooled version) | 
        
        
            | Operation altitude | 
            < 1000 m  above sea level (100 % load capacity) 
            > 1000 m  above sea level (with derating) | 
        
        
            | Relative air humidity | 
            5 % - 95 % (condensation not permitted) | 
        
        
            | Paint colour | 
            RAL 7035 (others on request) | 
        
        
            | Compliance with standards | 
            IEC 61800-2, IEC 60146-1-1, marine standars | 
        
        
            | Air cooled converter | 
        
        
            | Noise | 
            < 80 dB (A) at a distance of 1m from the cubicle | 
        
        
            | Ambient temp. for operation  | 
            + 0 ºC to + 40 ºC (higher with derating) | 
        
        
            | Degree of protection | 
            IP23 (others on request) | 
        
        
            | Main Options | 
        
        
            | Dynamic braking chopper, different communication modules, dv/dt filter, sinusoidal filter, input / output isolation switch, marine customization and others |