MV current sensor | INGEPAC™ LP CT 150

    INGEPAC™ LP CT sensors offer an alternative solution to conventional instrument transformers in a reduced space and at a more competitive cost, being a very complete solution for medium voltage environments.

    INGEPAC™ LP CT sensors are of the toroidal type for outdoor service and provide an analog voltage output signal proportional to the primary input current.

    INGEPAC™ LP sensors comply with the requirements defined in the IEC 61869-10 standards, thus guaranteeing a measurement accuracy of 0.2 S.

     

    Features

    • Accuracy: 0,2 S / 5 P 20
    • Accuracy in module: ±0,2%
    • Accuracy in argument: 10’
    • Operating conditions: -25 ºC up to 40 ºC
    • Transformation ratio: 500 A / 225 mV
    • Degree of protection: IP65
    • Material: epoxy
    • Primary voltages: 500 A

     

    Benefits

    • Measurement and protection accuracy
    • Smaller cost, size and weight
    • Very safe
    • Extensive dynamic range
    • Ease of installation

    • 16/06/2025

      CIRED

      CIRED has a reputation as one of the world’s top energy conferences. It’s where you will gain insight from electricity distribution expert...
    • 24/06/2025

      Electric & Hybrid Marine

      The world’s leading exhibition and conference for maritime electrification, decarbonization and GHG reduction solutions returns to Amsterdam &nd...

    Sie benötigen weitere Informationen?

    I agree to receive commercial communications from Ingeteam
    I have read and I agree to Ingeteam´s privacy terms.
    * You have to accept the Ingeteam´s privacy terms.
    Smart Grids - Social media

    Newsletter: Subscribe

    LinkedIn: View page

     

    Smart Grids - Contact

    E-mail: marketing.pga@ingeteam.com

    Phone: (+34) 944 039 600

    Address: Ingeteam Power Technology, S. A. - Parque Tecnológico de Bizkaia, Edificio 110 - Zamudio, 48170, Spain