| INGEDRIVE LV800 | 
        
            | General data | 
        
            | Inverter type | Two-level voltage source inverter with LV-IGBT power semiconductors | 
        
            | Rectifier type | Diode Front End (DFE) 12P, 18P, 24P 
 | Active Front End (AFE) | 
        
            | Main supply voltage range | 2x490 - 2x732 VAC | 480 - 690 VAC | 
        
            | Output power range (1) | 1495 kW - 8620 kW 
 | 1055kW - 9090 kW | 
        
            | Supply voltage tolerance | Tipically ± 10% | 
        
            | Supply frequency | 50 / 60 Hz (± 5 %) | 
        
            | Input power factor | 0.91 - 0.96 for DFE rectifiers 1 for AFE rectifiers
 | 
        
            | Output voltage | 0 to 440/660 VAAC 
 | 0 to supply voltage | 
        
            | Output frequency | 0 to 120 Hz (higher on request) | 
        
            | Efficiency  at rated load | Tipically > 0.97 for DFE rectifiers Tipically > 0.96 for AFE rectifiers
 | 
        
            | Motor types | Induction, synchronous or permanent magnet motor | 
        
            | Converter cooling | Water cooled with built-in water to water heat exchanger | 
        
            | Control properties | 
        
            | Control types | VC Vector Control / VF Voltage Frequency (2) | 
        
            | Static speed acc. (closed loop) (3) | <0.01% in field weakening / <0.01% at constant flow | 
        
            | Static torque acc. (closed loop) (3) | <1 % in field weakening / <1 % at constant flow | 
        
            | Static torque acc. (open lloop) (3) | <2 % in field weakening / <2 % at constant flow (for synchronous motors) 5 % in field weakening / <3 % at constant flow (for induction motors)
 | 
        
            | Torque response time | < 10 ms | 
        
            | Shaft torque ripple (3) | ± 1 % | 
        
            | Drive protection functions | Overcurrent, overvoltage and undervoltage monitoring; earth fault; short circuit detection and protection; semiconductor failure monitoring; cooling supervision; phase loss and others | 
        
            | Motor protection functions | Overload (4), Overspeed | 
        
            | Environmental Conditions | 
        
            | Ambient temp. for storage | - 20 ºC to  + 55 ºC (for empty cooling system in water cooled version) | 
        
            | Ambient temp. for transport | - 25 ºC to  + 55 ºC (for empty cooling system in water cooled version) | 
        
            | Operation altitude | < 2000 m  above sea level (100 % load capacity) > 2000 m  above sea level (with derating)
 | 
        
            | Relative air humidity | 5 % - 95 % (condensation not permitted) | 
        
            | Paint colour | RAL 7035 (others on request) | 
        
            | Compliance with standards | IEC 61800-2, IEC 60146-1-1, marine standars | 
        
            | Water cooled converter | 
        
            | Noise | <75 dB (A) at a distance of 1m from the cubicle | 
        
            | Ambient temp. for operation | + 0 ºC to + 45 ºC (higher with derating) | 
        
            | Degree of protection | IP44 (others on request) | 
        
            | Primary circuit coolants allowed | Seawater or freshwater | 
        
            | Primary coolant temp. allowed | + 0 ºC to + 38 ºC (higher with derating) | 
        
            | Primary circuit pressure drop | < 1 bar | 
        
            | Max. primary service pressure | 6 bar | 
        
            | Max. primary ΔT | 5º C | 
        
            | Secondary circuit coolant | Controlled pre-mixed liquid (fresh water < 10 µS/cm + anti-freezing) | 
        
            | Secondary circuit features | Redundant pump | 
        
            | Main Options | 
        
            | Dynamic braking chopper, different communication modules, dv/dt filter, sinusoidal filter, input / output isolation switch, marine customization and others |